DAM2(CM1) Moulded Case Circuit Breaker
DAM2(CM1) series the rated insulation voltage of the circuit breaker is 800V,it is suitable for the distribution network of AC 50Hz / 60Hz, rated working voltage of 690V and rated current of 1250A, to distribute power and protect circuit and power equipment from being damaged caused by overload , short-circuit, under-voltage and other fault. Also for protection infrequent conversion of the circuits and infrequent start of motor and overload, short circuit, under voltage. DAM2(CM1) circuit breaker can be mounted vertically (upright) or horizontally (transverse). DAM2(CM1) MCCB is suitable for isolation and the symbol is " ". DAM2(CM1) MCCB meets the standard: IEC60947-2 "low-voltage switchgear and control equipment
- Product Description
- Specifications
- Product Features
- More Details
Product Description
DAM2(CM1) series the rated insulation voltage of the circuit breaker is 800V,it is suitable for the distribution network of AC 50Hz / 60Hz, rated working voltage of 690V and rated current of 1250A, to distribute power and protect circuit and power equipment from being damaged caused by overload , short-circuit, under-voltage and other fault. Also for protection infrequent conversion of the circuits and infrequent start of motor and overload, short circuit, under voltage. DAM2(CM1) circuit breaker can be mounted vertically (upright) or horizontally (transverse). DAM2(CM1) MCCB is suitable for isolation and the symbol is " ". DAM2(CM1) MCCB meets the standard: IEC60947-2 "low-voltage switchgear and control equipment
Specifications
Model | Pole | Rated current (A) | Rated | Rated | Rated ultimate short - circuit breaking capacity (Icu) | Flashover | ||
Test voltage (V) | Icu (kA) | Ics (kA) | ||||||
DAM2(CM1)L-63 | 3 | 10、16、20、25、 | 400 | 500 | 400×1.10 | 25 | 18 | 0 |
DAM2(CM1)M-63 | 3、4 | 50 | 35 | |||||
DAM2(CM1)L-100 | 3、4 | 16、20、25、32、40、 | 400 | 800 | 30 | 22 | ≤50 | |
DAM2(CM1)M-100 | 2、3、4 | 50 | 35 | |||||
DAM2(CM1)H-100 | 3 | 85 | 50 | |||||
DAM2(CM1)L-100 | 3、4 | 690 | 10 | 5 | ||||
DAM2(CM1)M-100 | 2、3、4 | 20 | 10 | |||||
DAM2(CM1)L-225 | 3、4 | 100、125、140、 | 400 | 800 | 35 | 25 | ||
DAM2(CM1)M-225 | 2、3、4 | 50 | 35 | |||||
DAM2(CM1)H-225 | 3 | 85 | 50 | |||||
DAM2(CM1)L-225 | 3、4 | 690 | 10 | 5 | ||||
DAM2(CM1)M-225 | 2、3、4 | 20 | 10 | |||||
DAM2(CM1)L-400 | 3 | 225、250、315、 | 400 | 800 | 50 | 35 | ≤100 | |
DAM2(CM1)M-400 | 3、4 | 65 | 42 | |||||
DAM2(CM1)H-400 | 3 | 100 | 65 | |||||
DAM2(CM1)L-400 | 3 | 690 | 15 | 8 | ||||
DAM2(CM1)M-400 | 3、4 | 20 | 10 | |||||
DAM2(CM1)L-630 | 3 | 400、500、630 | 400 | 800 | 50 | 35 | ||
DAM2(CM1)M-630 | 3、4 | 65 | 42 | |||||
DAM2(CM1)H-630 | 3 | 100 | 65 | |||||
DAM2(CM1)L-630 | 3 | 6910 | 15 | 8 | ||||
DAM2(CM1)M-630 | 3、4 | 20 | 10 | |||||
DAM2(CM1)M-800 | 3 | 630、700、800 | 400 | 800 | 75 | 50 | ||
DAM2(CM1)H-800 | 3 | 100 | 65 | |||||
DAM2(CM1)M-800 | 3 | 4690 | 30 | 15 | ||||
DAM2(CM1)-1250 | 3 | 800、1000、1250 | 400 | 800 | 85 | 42 | ||
DAM2(CM1)-1250 | 3 | 690 | 25 | 12.5 |
Rated value of the circuit break
Note: 2-poles, 4-poles circuit breakers, divided into L, M, H, they have the same breaking index as M-type.
Characteristics of inverse time breaking action of circuit breakers over-current release for power distribution when every pole is power-on at the same time
No. | Test current | I/In | Set time | Initial state |
1 | Conventional non-tripping current | 1.05 | 2h(In>63A),1h(In≤63A) | Cold |
2 | Conventional non-tripping current | 1.30 | 2h(In>63A),1h(In≤63A) | Immediately after Test 1 |
Instantaneous action characteristic setting value of the circuit breaker for distribution is 10In±20%, and instantaneous action characteristic setting value of the circuit breaker for motor protection is 12In±20%.
Characteristics of inverse time breaking action of circuit breakers over-current release for motor protection when every pole is power-on at the same time
No. | I/In | Set time | Initial state | Remark |
1 | 1.0 | >2h | Cold | |
2 | 1.2 | ≤2h | Immediately after Test 1 | |
3 | 1.5 | ≤4min | Cold | 10≤n≤225 |
≤8min | 225 < in ≤ 630 | |||
4 | 7.2 | 4s≤T≤10s | Cold | 10≤In≤225 |
6s≤T≤20s | 225 < in ≤ 630 |
Accessories
Inverse time protection characteristic curve
Derating factors table of temperature changes
Model/Coefficient/Temperature | +40℃ | +45℃ | +50℃ | +55℃ | +60℃ |
DAM2(CM1)-63 | 1 | 0.94 | 0.88 | 0.80 | 0.72 |
DAM2(CM1)-100 | 1 | 0.95 | 0.89 | 0.84 | 0.76 |
DAM2(CM1)-225 | 1 | 0.96 | 0.91 | 0.87 | 0.82 |
DAM2(CM1)-400 | 1 | 0.94 | 0.84 | 0.80 | 0.73 |
DAM2(CM1)-630 | 1 | 0.93 | 0.88 | 0.83 | 0.76 |
DAM2(CM1)-800 | 1 | 0.93 | 0.88 | 0.83 | 0.76 |
DAM2(CM1)-1250 | 1 | 0.88 | 0.83 | 0.79 | 0.76 |
Model | H | H1 | H2 |
DAM2(CM1)-63L/3P | 74 | 89 | 19 |
DAM2(CM1)-63M/3P | 82 | 98.5 | 28.5 |
DAM2(CM1)-63H/3P | 82 | 98.5 | 28.5 |
DAM2(CM1)-63L/4P | - | - | - |
DAM2(CM1)-63M/4P | - | - | - |
DAM2(CM1)-63H/4P | - | - | - |
Product Features
■ Ambient air temperature: -5℃~+40℃, and average temperature in 24h is below +35℃.
■ Altitude: The altitude of the installation site is not more than 2000m.
■ Atmospheric conditions: The air relative humidity in the highest temperature +40℃ is not more than 50%; In the low temperature can have higher relative humidity. The maximum average relative humidity is 90%, while the average monthly minimum temperature is +25℃, and consider the temperature changes in product on the surface of the gel.

Videos
Related Solutions
-
Mining Equipment
The development of mining equipment has been driven by the need to extract resources from increasingly difficult-to-reach locations and to process larger quantities of ore with greater efficiency.
-
Rail Transportation
-
Power Industry
-
Mining Industry
The mining industry involves the extraction of valuable minerals or other geological materials from the Earth. The industry plays a crucial role in providing raw materials for various sectors, including construction, manufacturing, and energy production. However, the mining industry faces several challenges
-
Drilling Platform
Drilling platforms are essential structures in the oil and gas industry, enabling the extraction of hydrocarbons from beneath the Earth's surface. These platforms can be fixed or floating and are designed to withstand harsh marine environments.
-
Server Room
Server rooms are critical facilities that house computer servers, networking equipment, and data storage systems. They play a pivotal role in ensuring the smooth operation of IT infrastructure for businesses.
-
Building Automation
Building automation started with simple mechanical controls and has evolved into sophisticated digital systems that integrate various technologies to enhance building performance and occupant comfort.
-
Industrial Manufacturing
Today, the industry faces new challenges and opportunities, driven by technological advancements, globalization, and changing consumer demands.
Related Videos
-
DC solution
-
Motor protection solution
-
Electrical protection solution
-
New motor protection circuit breaker by Shanghai Dada Electrical Co., Ltd.
Introducing the new motor protection circuit breaker by Shanghai Dada Electrical Co., Ltd. This essential device provides protection for motors against overloads and short circuits, ensuring the safet
-
Understand the importance of molded case circuit breakers: focus on DAM1 series
The importance of reliable, efficient molded case circuit breakers (MCCB) in electrical installations cannot be overstated. The DAM1 series circuit breakers stand out as the first choice for professio
-
Shanghai Dada Electrical's new product is now launched!
Welcome to the world of DC Circuit Breakers! These innovative devices are designed to protect distribution and group systems with various loads. From drives with moderate starting currents like compre