LOW-VOLTAGE AIR CIRCUIT BREAKER(ACB)
DAA series Low Voltage Air circuit breaker air circuit breaker is suitable for the circuit of AC 50Hz/60Hz with rated service voltage 400V, 690V and rated service current up to 6300A.It is mainly used to distribute electric energy and protect circuits and electric equipment against over-load, under-voltage, short-circuit and single-phase earthing fault.
- Product Description
- Specifications
- Product Features
- More Details
Product Description
With intelligentized and selective protection functions, the breaker can improve the reliability of power supply, and avoid unnecessary power failure.The breaker is applicable for power stations, factories, mines (for 690V) and modern high- buildings, especially for the distribution system of intelligentized building.
Specifications
· Normal installation conditions
>> The circuit breakers DAA all be installed in accordance with the manufacturer’s instrucions.The vertical inclination of the circuit breakers DA All not exceed 5°
· Installation category
Rated operational voltage | 380/400V | 660/690V |
Installation category | ||
Electric circuit | ||
◆Main circuit | IV | IV |
◆Coil of under voltage release | ||
◆Pirmary coil power transformer | ||
◆Auxiliary circuit | III | III |
Degree of protection | Installation method | Accessories |
IP30 | Normal open mounting | |
IP40 | Mounted in a compartment of cubicle with additional door frame | door frame to be mounted by user |
IP54 | Mounted in a compartment of cubicle with additional door frame and transparent cover | door frame and transparent cove to be mounted by user |
· Pollution degree
Type | DAA1-1000 | DAA1-2000 | DAA2-3200 | DAA3-4000 | DAA4-6300 | |
Frame rated | 1000 | 2000 | 3200 | 4000 | 6300 | |
current Inm (A) | ||||||
Number of poles | 3,4 | 3,4 | 3,4 | 3,4 | 3,4 | |
Rated current In (A) | 200,400,630,800,1000 | 400,630,800,1000,1250,1600,2000 | 2000,2500,3200 | 4000 | 5000,6300 | |
Icu (kA)O-CO | 400V | 42 | 80 | 100 | 100 | 120 |
690V | 25 | 50 | 65 | 65 | 85 | |
Ics (kA)O-CO-CO | 400V | 30 | 50 | 65 | 65 | 100 |
690V | 20 | 40 | 50 | 50 | 80 | |
Icw(kA)O-CO | 400V | 20 | 50 | 65 | 65/80(MCR) | 85/100(MCR) |
690V | 20 | 40 | 50 | 50/65(MCR) | 65/75(MCR) | |
Rated current at N-pole In (A) | 50%In, 100%In | |||||
Inherent making& breaking time | 23-32ms | |||||
Operational performance (operations) | Electric life | 500 | ||||
Mechanical life | 9500 | |||||
Mounting mode | Fixed with drawable | |||||
Arcing distance(mm) | 0 | |||||
Intelligent controller | Standard type(M) Telecommunication type (H) | |||||
● Protection characteristics and functions of intelligent overcurrent controller
Protection characteristics of overcurrent controller
1. The setting value Ir (I/In) and error of the controller
Long delay | short delay | Instantaneous | Ground Fault | ||||
Ir1 | Ir2 | error | Ir3 | error | Ir4 | error | |
(0.4-1)In | (0.4-15)In | ±10% | In~50kA(Inm=2000A) | ±15% | Inm=2000~4000A | Inm=6300A | ±10% |
Note: When there is (required) three-stage protection at the same time, the setting values cannot be crossed.
2. Long-delay overcurrent protection inverse-time operation characteristics I²TL=(1.5lr1)²tL, and the operation time of (1.05~2.0)lr1 is shown in Table 4, and the time error is ±15%.
Note: tL-Long delay 1.5lrs setting time, TL-Long delay operation time.
Note: When there is (required) three-stage protection at the same time, the setting values cannot be crossed.
1.05Ir1 | 1.3Ir1 | 1.5Ir1 setting time (s) | 15 | 30 | 60 | 120 | 240 | 480 |
>2h non-operation | <1h opetation | 2.0Ir1 opetation time (s) | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
3. Short delay over-current protection characteristics
Short-time delay over-current protection is definite time limit. If the low multiple is required to be inverse time, the characteristic is: I²Ts=(8Ir1)²ts, ts is the general delay design time;
When the overload current >8Ir, it automatically converts to the definite time characteristic. Its definite time limit characteristic is shown in Table 5. The time limit error is ±15°C.
Product Features
· Normal operation conditions
>> The ambient air temperatures DA All not be over +40℃and below-5℃ and its average over a period of 24h hours does not exceed +35℃.
Altitude
>> The altitude of the site of installation does not exceed 2000m
>> Atmospheric conditions
Its relative humidity does not exceed 50% at a maximum temperature of +40℃,Higher relative humidity maybe permitted at lower temperature.The mean maximum value of the most humidity month is 90%,and the mean lowest temperature of this month is+25℃.Care should be taken
of moderate condensation which may occur on the surface of products due to variations in temperature.

Videos
Related Solutions
-
Power Industry
-
Building Automation
Building automation started with simple mechanical controls and has evolved into sophisticated digital systems that integrate various technologies to enhance building performance and occupant comfort.
-
Industrial Manufacturing
Today, the industry faces new challenges and opportunities, driven by technological advancements, globalization, and changing consumer demands.
Related Videos
-
DC solution
-
Motor protection solution
-
Electrical protection solution
-
New motor protection circuit breaker by Shanghai Dada Electrical Co., Ltd.
Introducing the new motor protection circuit breaker by Shanghai Dada Electrical Co., Ltd. This essential device provides protection for motors against overloads and short circuits, ensuring the safet
-
Understand the importance of molded case circuit breakers: focus on DAM1 series
The importance of reliable, efficient molded case circuit breakers (MCCB) in electrical installations cannot be overstated. The DAM1 series circuit breakers stand out as the first choice for professio