Home > Product > Electrical Protection Devices > Moulded Case Circuit Breaker > DAM1-2000








The new DAM1-2000 series Moulded Case Circuit Breaker, with modular, intelligent, miniaturization, easy installation, replacement concept, modular intelligent controller, communication function and measurement function, new modular manual mechanism and new modular electric mechanism, the core electric mechanism after hundreds of thousands of market rigorous assessment and practical application of the framework of the same organization, The contact system has no cross section from the incoming line end to the outgoing line end, so as to achieve better breaking and short-time resistance to current and temperature rise. The arc extinguishing chamber adopts high-density cascade grid and double extinction
The control technology of the arc chamber ensures the reliability of current breaking. Switch installation: fixed and drawer type DAM1E-2000 series Moulded Case Circuit Breaker (hereinafter referred to as circuit breaker), rated insulation voltage of 1000V, Suitable for AC 50Hz/60Hz, rated working voltage AC3801400/415V, AC500V, AC660/690V, AC800V, rated working current 800A, 1000A, 1250A, 1600A, 2000A circuit, used to distribute power. In addition to overload long delay inverse time limit, short circuit short delay fixed time limit, short circuit short delay inverse time limit, short circuit instantaneous, grounding, overload and alarm, alarm not trip function, can protect the line and power equipment from damage, It also has the current, voltage, power, power frequency, life, opening and closing state, operation times and other information of the feedback product to the host computer or other energy efficiency management system, which is used for the detection and monitoring of the circuit breaker, reducing the operation and maintenance cost of the power grid, and providing the necessary data for the future energy efficiency system.
DAM1Z-2000 series Moulded Case type circuit breaker (hereinafter referred to as circuit breaker), rated insulation voltage is 1200V, suitable for rated working voltage DC500V(2P series), DC60OV(2P series), DC750V(3P series), DC1000V(4P series), DC1200V(4P series), In the circuit with rated working current 800A.1000A, 1250A, 1500A, 1600A, 2000A, it is used to distribute electric energy, and protect the overload, short circuit, and undervoltage (with undervoltage trip device) of the line and power supply equipment.
Conforming to the standard :IEC60947-2, GBIT14048.2.
| ● Main technical parameters | ||||||
| Frame current Inm | 2000A | |||||
| Rated current In | DAM1-2000/DAM1E-2000 | 800A、1000A、1250A、1600A、2000A | ||||
| DAM1Z-200 | 800A、1000A、1250A、1500A、1600A、2000A | |||||
| Rated voltage Ue (V) | DAM1-2000/DAM1E-2000 | AC380/400V/415、AC500 AC660/690、AC800V | ||||
| DAM1Z-2000 | DC500V、DC600V、DC750V、 DC1000V、DC1200V | |||||
| Usage categories | A (thermal magnetic type)/B (electronic type) | |||||
| Rated impact voltag Uimp | 12kV | |||||
| Rated insulation voltage Ui | DAM1-2000/DAM1E-2000 | 1000V | ||||
| DAM1Z-2000 | 1200V | |||||
| Power frequency withstand votage (1 minute) | 3500V | |||||
| Dividing ability | Model | Code name | L ( Icu/Ics ) | M ( Icu/Ics ) | H ( Icu/Ics ) | |
| Rated ultimate breaking capacity;Icu (kA) /Rated operating breakingcapacity:Ics (kA) | DAM1-2000 DAM1-2000 |
AC380/400V/415V | 70/70 | 100/100 | 100/100 | |
| AC500V | 50/50 | 70/70 | 85/70 | |||
| AC660/690V | 20/20 | 35/35 | 50/42 | |||
| AC800V | / | / | 30/20 | |||
| DAM1Z-2000 | DC500V (2P series connection) | / | 70/70 | / | ||
| DC600V (2P series connection) | / | 35/35 | / | |||
| DC750V (3P series connection) | / | 70/70 | / | |||
| DC1000V (4P series connection) | / | 70/70 | / | |||
| DC1200V (4P series connection) | / | 35/35 | / | |||
| ·Derating coefficient table after product temperature changes and altitude changes | ||||||
| Ambient temperature drop coefficient table of DAM1(Z)-2000 plastic circuit breaker | ||||||
| Ambient humidity | Correction factor | Ambient humidity | Correction factor | Ambient humidity | Correction factor | |
| 40℃ | 1 | 50℃ | 0.94 | 60℃ | 0.83 | |
| 45℃ | 0.97 | 55℃ | 0.85 | 70℃ | 0.75 | |
| Note: 1. The above darating coefficienis are measured under frame current; 2. When the operating environment is lower than +40℃, the product can be used normally without derating: |
||||||
| DAM1(Z)-2000 plastic circuit breaker high altitude derating coefficient table | ||||||
| Altitude(m) | 2000 | 2500 | 3000 | 3500 | 4000 | 4500 |
| Power frequency withstand voltage (V) | 3500 | 3500 | 3150 | 3000 | 2800 | 2650 |
| Average insulation level(V) | 1000 | 1000 | 900 | 850 | 810 | 770 |
| Maximum operating current (V) | 800 | 800 | 720 | 670 | 630 | 600 |
| Maximum operating current(V) | 690 | 690 | 620 | 580 | 550 | 520 |
| Working current correction coefficient | / | / | 0.98 | 0.97 | 0.95 | 0.94 |
DAM1-2000 series Moulded Case type circuit breaker (hereinafter referred to as circuit breaker), rated insulation voltage is 1200V, suitable for rated working voltage DC500V(2P series), DC60OV(2P series), DC750V(3P series), DC1000V(4P series), DC1200V(4P series), In the circuit with rated working current 800A.1000A, 1250A, 1500A, 1600A, 2000A, it is used to distribute electric energy, and protect the overload, short circuit, and undervoltage (with undervoltage trip device) of the line and power supply equipment.
Circuit breakers are essential for protecting power systems from overloads and short circuits. Modern advancements, such as multi-chip current sharing and IoT integration, enhance their efficiency, safety, and reliability. Smart circuit breakers enable real-time monitoring and predictive maintenance, reducing downtime. Future trends focus on intelligence and sustainability, leveraging AI and eco-friendly designs. By adopting these […]
Today, the industry faces new challenges and opportunities, driven by technological advancements, globalization, and changing consumer demands.
Building automation started with simple mechanical controls and has evolved into sophisticated digital systems that integrate various technologies to enhance building performance and occupant comfort.
Circuit breakers are critical in rail transportation, ensuring the safety and reliability of electrical systems in trains and infrastructure. Modern circuit breakers feature advanced technologies like fast fault detection and IoT integration, enabling real-time monitoring and predictive maintenance. These innovations minimize downtime and enhance operational efficiency. Additionally, compact and durable designs are tailored to withstand […]
Server rooms are critical facilities that house computer servers, networking equipment, and data storage systems. They play a pivotal role in ensuring the smooth operation of IT infrastructure for businesses.
Drilling platforms are essential structures in the oil and gas industry, enabling the extraction of hydrocarbons from beneath the Earth's surface. These platforms can be fixed or floating and are designed to withstand harsh marine environments.
The mining industry involves the extraction of valuable minerals or other geological materials from the Earth. The industry plays a crucial role in providing raw materials for various sectors, including construction, manufacturing, and energy production. However, the mining industry faces several challenges
The development of mining equipment has been driven by the need to extract resources from increasingly difficult-to-reach locations and to process larger quantities of ore with greater efficiency.

Do you need a professional team to provide you with solutions? Contact us for a quote